Commissioning
Powerfailureduringthebootprocess
TheUPSserviceisnotyetactiveatthistime.TheUPSautomaticallyswitchestobatteryoperation,thus
bridgingthepowerfailure.ThePCisbootedupinbatterymode.DuringaprolongedpowerfailuretheUPS
servicetakesovercontrolafterthestartandstartsshuttingdownthesystem.
RestorationofsupplyandrepeatedpowerfailuresduringUPSshutdown
ThefollowingdiagramshowsacaseinwhichtheUPSserviceinitiatesashutdownandthesupplyis
restoredduringtheshutdown.
OncetheUPSservicehasinitiatedtheshutdownthisprocesscannotbestoppedandmustbecompleted.
RepeatedpowerfailuresduringtheshutdownarebridgedbytheUPS.InordertoenabletheIPCtorestart
theexternalpowersupplyisinterruptedbriefly(afewseconds).
CX210009x462 Version1.1