Mountingandwiring
4.2.2 ConnectionofCX29000192SmartBattery
TheCX21000914UPSPowerSupplyUnitstoresitschargeinaCX29000192SmartBattery.Thisisto
capableofsupportingtheCXsystemforlongerperiodsincaseofapowerfailure.Inadditionafurther
device,e.g.acontrolpanel,canbesuppliedwith24V.TheSmartBatteryisconnectedtothepowersupply
unitbytwocables:
1. Powercable(+24V,0V,earth)
2. Datacable(RJ45networkpatchcableCAT5)
Neithercableshouldbelongerthan5meters.ItisthuspossibletoplacetheSmartBatteryinasuitable
positioninthecontrolcabinet.
Theplugconnectorsforthepowercablingaresuppliedasasetwiththepowersupplyunitandcanbe
orderedasasparepart.
Apowerfailsignalcanthenadditionallybefedoutoftheplugconnectoronthepowersupplyunitfor
externalevaluation.