Commissioning
Setting/command Area Defaultvalue Description UPSsoft
warever
sion
Delaytimeforswitchingoff
theUPS[s]:
Hardware
dependent;
seetable
below
180 ThePCmusthaveproperlyshut
downwithinthistime.Aninternal
timerintheUPSmeasuresthetime
fromwhentheOSbegantoshut
down.Oncethistimehaselapsed,
theUPSswitchesoffitsoutputsin
ordertosavebatterycharge.Make
surethatyouhavenotselectedtoo
smallavalue.Theavailabledelay
timesdifferfromdevicetodevice
andarereadfromthedeviceand
displayedinthecombobox.The
UPSservicemustbeconfigured
andstartedupwiththeappropriate
UPSmodeltomakethispossible.
v1.0.0.48
Advanced... Advancedshutdownorendof
sessionoptionsforsystemswithout
softpowerofffunctionality(S5)
(e.g.NT4).Seealsounder:
Advanced Settings [}56].The
optionisnotavailableinsystems
withthesoftpoweroffsupport
(deactivated).
v2.0.0.12
Factorysettings Allsettingsareresettotheirdefault
values.
OK Savesthesettingsandclosesthe
dialog.Pleasedonotforgetto
confirmthesettingsintheBeckhoff
UPSConfigurationdialog.
Cancel Discardsalleditablechangesand
closesthedialog.
*)UnderNT4thisoptionisonlyavailableifyouhaveinstalledtheMicrosoftWindowsTaskScheduler(under
IE4youselecttheTaskSchedulerunderAdditionalExplorerEnhancements,andunderIE5youselectthe
OfflineBrowsingPack).
ThetableprovidesabriefsummaryofthevariousdelaytimesforafewUPSmodels.
UPSmodel BeckhoffP24Vxxxx
UPS
Beckhoff24V
UPSonthe
CP903xcard
APCBackUPS
Pro280
APCSmartUPS
420
Availabledelaytimesin
[s]
20,30*,45*,60,90,180,
300,600*fromfirmware
version>=28.1.I
0,2,5,10,15,25,
40,60,90,120,
150,180,210,
240,270,600
20,180,300,
600
60,180,300,600
Importantinstructions!
ThedelaytimeconfiguredinthedialogischeckedagainintheUPSdrivershortlybeforetheOSshutdown.If
avaluethatisnotsupportedisfound,thenexthighervalueisautomaticallysenttotheUPS.
Example:
SupposeyouhavereplacedanoldBackUPSPro280withaSmartUPS420,andthatadelaytimeof20s
hadpreviouslybeenconfiguredinthedialog.ThenewUPSwillthenautomaticallybeswitchedoffaftera
delaytimeof60s.
AtthesametimetheUPSdriverwillwriteawarningintothewindowseventlog(underApplication).
CX210009x4 55Version1.1