Page 34 of 44 Version : 2.01 Date : 18.12.95
Example:
Initialization of communication 3 as a free communication with 2 telegrams. Base addres for
the output area is 400h base address for the input area is 210h
channel length function empty argument
0
argument
1
argument
2
argument
3
call
09 0b 00 03 02 00,04 10,02
channel length function argument
0
comment
response
03 0b 00 ok
using this structure there is the possibility of a run-time change of module address and con-
trol byte. But this is restricted to phases when there are no active communications.