Beckhoff KL2612 Manuel d'utilisateur Page 3

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 2
Datasheet for KL2612, Version 1.1
Beckhoffand TwinCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms
of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Phone: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149,
http://www.beckhoff.com
Technical data
Technical data KL2612
Number of outputs
2 x change-over
Contact material
Gold-clad silver alloy
Switched voltage max.
125 V AC / 30 V DC
Switched current max.
5 A
Switched power max.
with resistive load
alternating voltage
0,5 A 125V AC
direct voltage
2 A 30V DC
Minimum permitted load
(approximate)
10 µA at 10mV
Reaction times
at rated load
Max. reaction time 4 ms
Max. release time 4 ms
max. bounce time 4 ms
Electrical isolation
500 V
eff
(K-bus/mains voltage)
K-bus current consumption
60 mA
Bit width in the process
image
2 A
Service life (operating
cycles) mechanical
10
8
cycles
Operating cycles electr.
(min.)
10
5
resistive load switches
at 30 V DC, 2 A
or 125 V AC, 0,5 A
Permitted operating
frequency at maximum
contact load
20 cycles / min
Contact resistance max. (new)
< 40 mOhm
Insulation resistance (min).
100 MOhm at 500 V DC
Test voltage between
open contacts
750 V (1 min. between open contacts)
Configuration
No address or configuration settings
Weight approx.
80 g
Operating temperature
C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95% without dew formation
Vibrations/Shock
resistance
according to IEC 68-2-6 / IEC 68-2-27
EMC resistance burst / ESD
According to EN 50082 (ESD, burst) / EN 50081
Installation position
any
Type of protection
IP20
Vue de la page 2