Beckhoff CX2100­00x4 Manuel d'utilisateur Page 20

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 45
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 19
Productoverview
Init
AfterswitchontheEtherCATslaveintheInitstate.Nomailboxorprocessdatacommunicationispossible.
TheEtherCATmasterinitializessyncmanagerchannels0and1formailboxcommunication.
PreOperational(PreOp)
DuringthetransitionfromInittoPreOp,theEtherCATslavecheckswhetherthemailboxhasbeencorrectly
initialized.MailboxcommunicationispossibleinthePreOpstate,butnoprocessdatacommunication.The
EtherCATmasterinitializesthesyncmanagerchannelsforprocessdata(fromsyncmanagerchannel2),the
FMMUchannelsand,iftheslavesupportsconfigurablemapping,PDOmappingorthesyncmanagerPDO
assignment.Inthisstatethesettingsfortheprocessdatatransferandperhapsterminalspecificparameters
thatmaydifferfromthedefaultsettingsarealsotransferred.
SafeOperational(SafeOp)
DuringtransitionbetweenPreOpandSafeOptheEtherCATslavecheckswhetherthesyncmanager
channelsforprocessdatacommunicationand,ifrequired,thedistributedclockssettingsarecorrect.Before
itacknowledgesthechangeofstate,theEtherCATslavecopiescurrentinputdataintotheassociatedDP
RAMareasoftheEtherCATslavecontroller(ECSC).
MailboxandprocessdatacommunicationarepossibleintheSafeOPstate;however,theslavemaintainsits
outputsinthesafestateanddoesnotoutputthem.Theinputdata,however,arealreadycyclicallyupdated.
Operational(Op)
BeforetheEtherCATmasterswitchestheEtherCATSlavefromSafeOptoOp,itmusttransmitalreadyvalid
outputdata.IntheOpstatetheslavecopiestheoutputdataofthemastertoitsoutputs.Processdataand
mailboxcommunicationispossible.
Boot
IntheBootstatetheslavefirmwarecanbeupdated.TheBootstatecanonlybereachedviatheInitstate.In
theBootstatemailboxcommunicationispossibleviatheFileAccessoverEtherCAT(FoE)protocol,butno
othermailboxcommunicationandnoprocessdatacommunicationispossible.
CX210000x420 Version1.0
Vue de la page 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 44 45

Commentaires sur ces manuels

Pas de commentaire