Beckhoff CX2020 Manuel d'utilisateur Page 25

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 47
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 24
Mountingandwiring
3.5 Powersupply
ThispowersupplyunitisequippedwithanI/Ointerface,whichpermitsconnectionoftheBeckhoffBus
Terminals.Thepowerissuppliedviatheupperspringloadedterminalslabelled“24V”and“0V”.
ThesupplyvoltagesuppliestheCXsystemanttheterminalBusandBusTerminalwithavoltageof24VDC
(15%/+20%).Thedielectricstrengthofthepowersupplyunitis500V
rms
.SincetheTerminalBus(Kand
Ebus)onlytransfersdata,aseparatepowersupplyisrequiredfortheBusTerminals.Thisisprovidedby
meansofthepowercontacts,whicharenotconnectedtothepowersupply.
Requirementsforthe24Vpowersupply
InordertoguaranteetheoperationoftheCPU(CX20x0module)andtheterminalstrandinallcases,the
powersupplymustsupply4Aat24V.
Theterminalsareimplementedinspringforcetechnology.Connectthecablesasfollows:
1. Openaspringloadedterminalbyslightlypushingwithascrewdriverorarodintothesquareopening
abovetheterminal.
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresecurelyand
permanently.