Commissioning
Embedded PC 31
Enable Automatic Shut Down:
If this switch is selected, then TwinCAT is stopped after an adjustable retention time, and "Windows XPe" is shut
down. Device 1 (here the CX1100) is switched off after the retention time has elapsed. Even when the power fails for
very short periods (<<10s) the system shuts down and the CX is switched off.
Problem: If the voltage returns after TwinCAT has stopped but while "Windows XPe" is still in the process of shutting
down, the CX remains on, but "Windows XPe" remains stopped.
The UPS is fully charged again. The voltage must remain switched off for long enough for the UPS to switch off, and
only after this will reboot take place.
Configuration 2:
"Enable Automatic Shutdown" and "No Abort" are active:
"CX1190 UPS" tab: